您現(xiàn)在的位置:首頁 > 產(chǎn)品信息 > 電力電纜
■ 產(chǎn)品標(biāo)準(zhǔn) Product Standard
GB/T12706.1-2002,等效采用IEC60502
GB/T12706.1-2002,equivalent to IEC60502
■ 用途 Usage
本產(chǎn)品適用于交流額定電壓(U0/U)0.6/1kV系統(tǒng)的輸配電線路
This product is sultable for use in rated AC voltage(U0/U)0.6/1kV system transmitting and distributing circuit.
■ 使用特性 Property for use
1. 既有遠(yuǎn)優(yōu)于PVC絕緣電纜的所有特性指標(biāo),有克服了物理交聯(lián)和其他化學(xué)交聯(lián)的弊端,并且完全達(dá)到或超過了GB及IEC規(guī)定的技術(shù)特性值。
It is for better than all property targets of PVC insulated power cable and has overcome the short comings of physical and chemical cross-linkage,and completely reaches or surpasses GB and IEC technical property value.
2. 電纜導(dǎo)體最高允許工作溫度為90℃;應(yīng)急超載工作溫度為130℃;短路時(5s)導(dǎo)體最高溫度為250℃。
The allowed max. cable conductor work temperature is 90℃;urgent excess work temperature is 130℃ for short circult(5s),max. conductor temperature is 250℃.
3. 電纜敷設(shè)時的環(huán)境溫度應(yīng)不低于0℃,如在0℃一下敷設(shè),應(yīng)對電纜預(yù)熱。
The environmental temperature for laying cable should be not less than 0℃,if alying under 0℃,the cable should be preheated.
4. 電纜彎曲半徑為:單芯電纜不小于電纜外徑的12倍;多芯電纜不小于電纜外徑的10倍。
The cable bend radius for single core should be not less than 12 times of overall cable diameter;for multi-core cable,not less than 10 times of overall cable diameter.
5. 載流量大,敷設(shè)不受落差限制。
The current-carrying capacity is large and not limited by drop during layig.
■ 電纜的型號 Type of cable
型號 Type |
名稱 Designation |
適用范圍 Application |
YJV |
銅芯交聯(lián)聚乙烯絕緣聚氯乙烯護套電力電纜 Copper conductor,XLPE insulated and PVC sheathed Electrical cable. |
室內(nèi)、隧道及電纜溝等場所,不能承受機械外力。 For laying indoors,in tunnels or cable trench,unable to beer external mechanical forces. |
YJLV |
鋁芯交聯(lián)聚乙烯絕緣聚氯乙烯護套電力電纜 Aliuminium conductor,XLPE insulated and PVC sheathed Electrical cable. |
|
YJY |
銅芯交聯(lián)聚乙烯絕緣聚乙烯護套電力電纜 Copper conductor,XLPE insulated and PE sheathed Electrical cable. |
|
YJLY |
鋁芯交聯(lián)聚乙烯絕緣聚乙烯護套電力電纜 Aliuminium conductor,XLPE insulated and PE sheathed Electrical cable. |
型號 Type |
名稱 Designation |
適用范圍 Application |
YJV22 |
銅芯交聯(lián)聚乙烯絕緣鋼帶鎧裝聚氯乙烯護套電力電纜 Copper conductor,XLPE insulated,steel tape armoured and PVC sheathed Electrical cable. |
室內(nèi)、隧道、電纜溝、直埋及易腐蝕場合,能承受機械外力的場所。 Indoors,tunnels,cable canal,vertically burying and easy to corrode places,can bear mechanical pressure. |
YJLV22 |
鋁芯交聯(lián)聚乙烯絕緣鋼帶鎧裝聚氯乙烯護套電力電纜 Aluminium conductor,XLPE insulated,steel tape armoured and PVC sheathed Electrical cable. |
|
YJV23 |
銅芯交聯(lián)聚乙烯絕緣鋼帶鎧裝聚乙烯護套電力電纜 Copper conductor,XLPE insulated,steel tape armoured and PE sheathed Electrical cable. |
|
YJLV23 |
鋁芯交聯(lián)聚乙烯絕緣鋼帶鎧裝聚乙烯護套電力電纜 Aluminium conductor,XLPE insulated,steel tape armoured and PE sheathed Electrical cable. |
|
YJV32 |
銅芯交聯(lián)聚乙烯絕緣細(xì)鋼絲鎧裝聚氯乙烯護套電力電纜 Copper conductor,XLPE insulated,steel wire armoured and PVC sheathed Electrical cable. |
垂直敷設(shè),可承受機械拉力,但不承受壓力。 Vertically laying,can bear mechanlcal pulling force,but not pressure. |
YJLV32 |
鋁芯交聯(lián)聚乙烯絕緣細(xì)鋼絲鎧裝聚氯乙烯護套電力電纜 Aluminium conductor,XLPE insulated,steel wire armoured and PVC sheathed Electrical cable. |
|
YJV33 |
銅芯交聯(lián)聚乙烯絕緣細(xì)鋼絲鎧裝聚烯護套電力電纜 Copper conductor,XLPE insulated,steel wire armoured and PE sheathed Electrical cable. |
|
YJLV33 |
鋁芯交聯(lián)聚乙烯絕緣細(xì)鋼絲鎧裝聚乙烯護套電力電纜 Aluminium conductor,XLPE insulated,steel wire armoured and PE sheathed Electrical cable. |
■ 生產(chǎn)范圍 Preduction Range of cable
型號 Type |
芯數(shù) No. fo cores |
標(biāo)稱截面 Nominal cross-scetional area mm2 |
|
銅導(dǎo)體 Copper Conductor |
鋁導(dǎo)體 Aluminium Conductor |
||
YJV YJY — YJV22 YJY23 |
— YJLV YJLV YJLV22 YJLV23 |
1* |
1.5~800 2.5~800 10~800 |
YJV YJY — YJV22 YJV23 YJV32 YJV33 |
— YJLV YJLY YJLV22 YJLV23 YJLV32 YJLV33 |
2 |
1.5~400 2.5~400 2.5~400 10~400 |
YJV YJY — YJV22 YJV23 YJV32 YJV33 |
— YJLV YJLY YJLV22 YJLV23 YJLV32 YJLV33 |
3 |
1.5~400 2.5~400 2.5~400 10~400 |
型號 Type |
芯數(shù) No. fo cores |
標(biāo)稱截面 Nominal cross-scetional area mm2 |
|
銅導(dǎo)體 Copper Conductor |
鋁導(dǎo)體 Aluminium Conductor |
||
YJV YJY — YJV22 YJV23 YJV32 YJV33 |
— YJLV YJLY YJLV22 YJLV23 YJLV32 YJLV33 |
4 |
1.5~400 2.5~400 2.5~400 10~400 |
YJV YJY — YJV22 YJV23 — YJV32 YJV33 |
— YJLV YJLY — YJLV22 YJLV23 YJLV32 YJLV33 |
3+1 |
1.5~400 4~400 1.5~400 4~400 10~400 |
YJV YJY — YJV22 YJV23 — YJV32 YJV33 |
— YJLV YJLY — YJLY22 YJLV23 YJLV32 YJLV33 |
5 |
1.5~400 2.5~400 1.5~400 2.5~400 10~400 |
YJV YJY — YJV22 YJV23 — YJV32 YJV33 |
— YJLV YJLY — YJLY22 YJLV23 YJLV32 YJLV33 |
4+1 |
1.5~400 4~400 1.5~400 4~400 10~400 |
YJV YJY — YJV22 YJV23 — YJV32 YJV33 |
— YJLV YJLY — YJLY22 YJLV23 YJLV32 YJLV33 |
3+2 |
1.5~400 4~400 1.5~400 4~400 10~400 |
注:單芯鎧裝電纜適用于直流系統(tǒng),若用于交流系統(tǒng),應(yīng)采用非磁性材料鎧裝或隔磁措施。
The armoured single-core cables are used for d.c. system only.As for a.c. system,non-magnetic armour material should be used,or magnetic isolation should be applied.
■ 電纜參數(shù) Product data table
0.6/1kV單芯交聯(lián)聚乙烯絕緣聚氯乙烯/聚乙烯護套電力電纜
1.6/1kV 1-Core,XLPE insulated PVC/PE Sheathed Power Cable
注:*表示緊壓導(dǎo)體
*Compacted conductor
0.6/1kV兩芯交聯(lián)聚乙烯絕緣聚氯乙烯/聚乙烯護套電力電纜
0.6/1kV 2-Core,XLPE Insulated PVC/PE Sheathed Power Cable
注:*表示緊壓導(dǎo)體
* Compacted conductor
0.6/1kV三芯交聯(lián)聚乙烯絕緣聚氯乙烯/聚乙烯護套電力電纜
0.6/1kV 3-Core,XLPE Insulated PVC/PE sheathed Power Cable
注:*表示緊壓導(dǎo)體
* Compacted conductor
0.6/1kV四芯交聯(lián)聚乙烯絕緣聚氯乙烯/聚乙烯護套電力電纜
0.6/1kV 4- Core,XLPE Insulated PVC/PE sheathed Power Cable
注:*表示緊壓導(dǎo)體
* Compacted conductor
0.6/1kV三芯交聯(lián)聚乙烯絕緣聚氯乙烯/聚乙烯護套電力電纜
0.6/1kV 3-Core,XLPE Insulated PVC/PE sheathed Power Cable
注:*表示緊壓導(dǎo)體
* Compacted conductor
0.6/1kV五芯交聯(lián)聚乙烯絕緣聚氯乙烯/聚乙烯護套電力電纜
0.6/1kV 5-Core,XLPE Insulated PVC/PE sheathed Power Cable
注:*表示緊壓導(dǎo)體
* Compacted conductor
0.6/1kV 4+1芯交聯(lián)聚乙烯絕緣聚氯乙烯/聚乙烯護套電力電纜
0.6/1kV 4+1-Core,XLPE Insulated PVC/PE Sheathed Power Cable
注:*表示緊壓導(dǎo)體
* Compacted conductor
0.6/1kV 3+2芯交聯(lián)聚乙烯絕緣聚氯乙烯/聚乙烯護套電力電纜
0.6/1kV 3+2-Core,XLPE Insulated PVC/PE Sheathed Power Cable
注:*表示緊壓導(dǎo)體
* Compacted conductor
導(dǎo)體標(biāo)稱截面 Nominal Cross sectional area of conductor mm2 |
20℃時導(dǎo)體最大直流電阻(Ω/km) Max.D.C. resistance of conductor at 20℃ |
||
銅 Copper |
鋁 Aluminium |
||
1 |
18.1 |
— |
|
1.5 |
12.1 |
— |
|
2.5 |
7.41 |
12.1 |
|
4 |
4.61 |
7.41 |
|
6 |
3.08 |
4.61 |
|
10 |
1.83 |
3.08 |
|
16 |
1.15 |
1.91 |
|
25 |
0.727 |
1.20 |
|
35 |
0.524 |
0.868 |
|
50 |
0.387 |
0.641 |
|
70 |
0.268 |
0.443 |
|
95 |
0.193 |
0.320 |
|
120 |
0.153 |
0.253 |
|
150 |
0.124 |
0.206 |
|
185 |
0.0991 |
0.164 |
|
240 |
0.0754 |
0.125 |
|
300 |
0.0601 |
0.100 |
|
400 |
0.0470 |
0.0778 |
|
500 |
0.0366 |
0.0605 |
|
630 |
0.0283 |
0.0469 |
|
800 |
0.0221 |
0.0367 |
|
工頻交流電壓試驗 Power frequency A.C. voltage tset kV/5min |
試驗電壓3.5Kv/5min Test voltage 3.5kV/5min |
IEC推薦的載流量大為降低,截面選擇宜適當(dāng)放大。
The screen-coppeer-tape and steel wire (including all copper wire for magnetism seperation) of single-core steel wire armored power cable for AC system must be connectted to earth well and effectivity.
The current carying capacity is calculated by formulas of IEC.It is advised in the new edition of GB/T12706 that the current carrying capacity of steel wire armored power cable with special structure is lower than that in IEC standard,so the cross-section should be enlarged appopriately.
■電纜敷設(shè)運行條件 Installation and Operation Condition of Cable
在空氣中敷設(shè) In air
1. 單芯電纜平行敷設(shè)時中心距離:185mm2及以下為電纜直徑的2倍;240mm2及以上為90mm。
2. 周圍環(huán)境空氣溫度:30℃。
3. 導(dǎo)體的長期最高工作溫度:90℃。
1. The distance between cable centers of single-core cables laid in paralled:cross sectional area of conductor ≤185mm2: 2 times of the cable diameter;cross-sectional area of conductor≥240mm2:90mm.
2. Ambient air temperature:30℃.
3. Max. contionous operating temperature of conductor:90℃.
不同環(huán)境溫度下載流量的修正系數(shù):
Current carrying rating factors for different ambient air temperature:
環(huán)境溫度 Ambient air temperature |
20℃ |
25℃ |
30℃ |
35℃ |
40℃ |
45℃ |
修正系數(shù) Rating factor |
1.09 |
1.04 |
1.00 |
0.95 |
0.90 |
0.84 |
直埋敷設(shè) Direect in the ground
1. 單芯電纜不接觸敷設(shè)時電纜中心距離為電纜直徑的2倍。
2. 土壤溫度:25℃
3. 導(dǎo)體的長期最高工作溫度:90℃
4. 土壤熱阻系數(shù):1.0℃.m/W。
5. 直埋深度:0.7m。
1. The single-core cables are installed separately,the distance between the cable center is 2 times of the cablediameter.
2. Soil temperature:25℃
3. Max. contionous operating temperature of conductor:90℃.
4. Thermal resistivity of soil: 1.0℃.m/W.
5. Depth of Direct-buried:0.7m.
不同土壤溫度下載流量的修正系數(shù):
Current carrying rating factors for different soil temperature:
土壤溫度 Soil temperature |
20℃ |
25℃ |
30℃ |
35℃ |
40℃ |
修正系數(shù) Rating factor |
1.04 |
1.0 |
0.96 |
0..92 |
0.87 |
上一篇:一步法硅烷交聯(lián)電力電纜 |